Flow meter / flow switch RA 87 / FA 87

Flow meter / flow switch RA 87 and FA 87 are based on the variable area float principle.

Flow meter / flow switch RA 87 / FA 87 for liquids and gases
  • calibrated borosilicate measuring cone
  • armature completely made of stainless steel
  • perspex half-shell as shatter protection
  • reliable due to simple mode ofoperation
  • scales specific for the media to be measured
Delivery time:
approx. 4 weeks
<<<<<<<<<<Delivery time
approx. 4 weeks

Variable area flow meter / flow switch RA 87 / FA 87

Measuring range

0,5 - 200 l/h
0,1 - 16 m³/h

Operating pressure max. 10 bar
Accuracy class 1.6 according to VDI/VDE 3513 page 2 (08/2008)
Connection

Internal thread or pipe fitting (RA87)
Flange (FA87)

Temperature resistance up to 100 °C
EX version according to Atex available

Installation of the flow meter / flow switch RA 87 / FA 87

In pipelines the RA 87 is installed by means of pipe unions and the FA 87 is mounted between flanges. The borosilicate glass measuring cone is located inside a protective stainless steel tube with an inspection window. All parts in contact with the measured medium are made of stainless steel 1.4571.

Application

VA flow meters RA 87 and FA 87 are most suitable for the flow measurement of transparent liquids and gases. Each unit is customized with a scale specific for the medium to be measured. RA 87 and FA 87 are mainly used in the chemical industry, in water treatment plants, in the food industry, industrial furnace construction and in other plant engineering applications.

By installation of electrical limit value switches, which are adjustable throughout the entire measuring range, this devices can be used as detectors. By installing an linear displacement sensor an output signal can be generated which is proportional to the height setting of the flow meter.

Certificates

  • EC registration certificate
  • Statement of application of directive 94/9/EC
  • EU-Declaration of Conformity